- Heat pumps
- Air-to-water heat pump
E8
Baxi E8 on an HP40/HP50 heat pump: water flow failure

Risk level
Medium
Proceed carefully and stop if the check is unclear.
Urgency
Medium
Quick answer
On Baxi HP40 and HP50 monobloc heat pumps, E8 means water flow in the circuit is too low. Check that the pressure gauge reads above 1 bar and the valves are open; then switch the unit off and on once.
Safety first
Stop and check this first
- Baxi says that if the off and on reset does not clear the fault, you should contact your supplier. Do not open the unit: with the service panel removed some components are live and the R32 refrigerant is flammable.
Safe checks you can perform
- Circuit pressure
- Shut off valves and restart
- Filter, purging, pump and vessel
Leave these tasks to a qualified professional
- Do not attempt this professional task: Full hydraulic check
- Do not attempt this professional task: Fuses and backup heater if it happened in defrost
What a technician must be able to justify
Technician visit
These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.
These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.
Full hydraulic check
What they doThe installer checks valves, filter, purging, pressure, pump speed and expansion vessel following Baxi's list.
They must show youthe final pressure above 1 bar, the clean filter and the pump speed setting.
In writingwhat they found, what they corrected and any part replaced, with its part number.
Fuses and backup heater if it happened in defrost
What they doIf E8 appeared during defrost, the installer checks the backup heater wiring and fuses and the pump and PCB fuses.
They must show youthe fuses checked and their condition.
In writingthe result of the check and the operating test without E8.
Before accepting a part or repair
Nothing has been shown yet. Do not accept a part swap based on the code alone.
Follow these steps
Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.
Circuit pressure
- Who:
- you.
- How:
- read the heating circuit pressure gauge with the system at rest.
- Result that matters:
- Baxi states the water pressure must be above 1 bar.
- If it is below 1 bar:
- lack of water explains E8; ask the installer to refill and find the loss.
- If it is above 1 bar:
- low pressure is ruled out; valves, filter, air or pump remain.
- Evidence to keep:
- a photo of the gauge with the date.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
Shut off valves and restart
- Who:
- you, without opening the unit.
- How:
- check that the visible shut off valves on the water circuit are fully open. Then switch the unit off and on again, the reset Baxi describes.
- Result that matters:
- whether E8 returns after the reset.
- If a valve was closed and E8 does not return:
- that was the cause.
- If E8 returns:
- do not keep resetting; call the installer. After three E8 events the unit moves to E0.
- Evidence to keep:
- a note of the valve found and how many times E8 appeared.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
Filter, purging, pump and vessel
- Who:
- the installer.
- How:
- they clean the water filter, purge air, set the pump to its highest speed, check the expansion vessel, compare circuit resistance with the pump curve and check the pump and PCB fuses.
- Result that matters:
- the restored flow and the condition of each item.
- If the filter was dirty or there was air:
- a hydraulic cause is confirmed.
- If everything is fine and E8 persists:
- the pump, a fuse or the circuit resistance is the suspect.
- Evidence to keep:
- a job sheet with what was checked and a photo of the filter.
Opening the unit exposes live parts: Baxi requires isolation from the mains before touching terminals. R32 refrigerant is flammable. Installer only.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
Still not solved
If the error persists, stop here. See what the technician must do and show you.
Where this code applies
A code is meaningful only inside the right product and version context.
Primary scope
- System
- Heat pumps
- Brand
- Baxi
- Product type
- Air-to-water heat pump
Known code variants
- AEG E8
- AEG E822
- AEG hob E8
- Baxi heat pump E8
- Baxi HP40 E8
- Baxi HP50 E8
- Beko BM1WU E8 code
- Beko lavadora E8
- Beko washer E8
- Beko washing machine E8 not taking water
- Bosch Compress E8
- Bosch E8 caudal de agua
- Bosch E8 water flow
- Bosch heat pump E8
- código E8 Beko BM1WU
- Compress 2000 AWF E8
- CS2000AWF E8
- E08
- E 8
- E822
- E8xx
- E:8
- error E8 aerotermia Bosch
- Gree E8
- Junkers E8
- lavadora Beko E8 no coge agua
- placa AEG E8
What it means
Baxi links E8 to a water flow failure in the hydraulic circuit. Its action list covers closed shut off valves, a dirty water filter, air in the system, water pressure below 1 bar, pump speed, a broken expansion vessel, circuit resistance too high for the pump and blown pump or PCB fuses. If it appears during defrost, it also points at the backup heater supply. The code does not say which one it is.
Warnings and stop conditions
- Mediumsource verified
Baxi says that if the off and on reset does not clear the fault, you should contact your supplier. Do not open the unit: with the service panel removed some components are live and the R32 refrigerant is flammable.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
Symptoms and causes
Probable causes · in order
- Closed valves or dirty filterCommon
Baxi starts with the circuit shut off valves and the water filter. They are the most common after work on the system or when the filter was never cleaned.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
- Low pressure or air in the systemCommon
Below 1 bar or with air, the pump cannot move enough water. A look at the gauge and purging separate it.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
- Pump, expansion vessel or circuit designPossible
A pump on low speed, a broken expansion vessel or a circuit with more resistance than the pump can overcome give E8 with correct pressure.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
- Fuses or backup heater during defrostPossible
If it shows during defrost, Baxi asks to check the backup heater supply and fuses, plus the pump and PCB fuses.
Evidence: Baxi HP40/HP50 monobloc air to water heat pump, installation and service manual 784570
Virtual technician
Does E8 still appear after these checks?
Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.