81-00
Daikin Altherma 4 H F 81-00: water sensor after BUH fault

Risk level
High
Professional inspection is recommended.
Urgency
High
Quick answer
Code 81-00 on a Daikin Altherma 4 H F means the exit water temperature thermistor after the backup heater (BUH), designated R2T, is malfunctioning. Both the heat pump and backup heater stop for space heating and hot water. Check [11] Malfunction history and call your installer.
Safety first
Stop and check this first
- Do not open the indoor unit or switch box: Daikin requires disconnecting all power supplies for more than 10 minutes and measuring less than 50 V DC before touching internal electrical components near the backup heater and PCB.
- Never jumper, bypass, or remove thermistor R2T to force the backup heater or heat pump to run; Daikin mandates operating the unit with all thermistors and safety devices connected to prevent overheating.
Safe checks you can perform
- Check the 81-00 long description and log timestamps in [11] Malfunction history
- Inspect water temperature values in [6.3] Sensors and note that emergency BUH operation is blocked
- Retrieve the installer contact from [6.2] Dealer information for an R2T sensor inspection
Leave these tasks to a qualified professional
- Do not attempt this professional task: Discharge capacitors safely and measure thermistor R2T (Backup heater Water OUT) resistance
- Do not attempt this professional task: Verify R2T harness continuity, thermal clip seating after the backup heater, and automatic reset
What a technician must be able to justify
Technician visit
These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.
These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.
Discharge capacitors safely and measure thermistor R2T (Backup heater Water OUT) resistance
What they doAn authorised Daikin technician must disconnect all power supplies for more than 10 minutes, verify less than 50 V DC inside the switch box, unplug thermistor R2T, and measure its resistance with a multimeter against the service manual temperature-resistance table.
They must show youthe multimeter resistance reading of thermistor R2T and the corresponding water pipe temperature measurement.
In writingmeasured R2T resistance in ohms, reference temperature in degrees Celsius, and whether R2T was replaced or retained.
Verify R2T harness continuity, thermal clip seating after the backup heater, and automatic reset
What they doThe technician must inspect the R2T sensor lead and connector pins for heat damage or corrosion, confirm the probe is properly seated on the backup heater outlet pipe, and verify that 81-00 clears automatically and both heat pump and backup heater resume operation.
They must show youthe live water outlet temperature reading on the controller after reconnecting or replacing R2T while heating and domestic hot water resume.
In writingwritten confirmation of R2T harness continuity, sensor seating inspection, and normal space heating and domestic hot water operation with 81-00 cleared.
Before accepting a part or repair
Nothing has been shown yet. Do not accept a part swap based on the code alone.
Follow these steps
Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.
Check the 81-00 long description and log timestamps in [11] Malfunction history
- Who:
- The homeowner or operator at the indoor user interface.
- How:
- Select the 81-00 alert on the home screen to view the long description, then set the user permission level to advanced end user and open [11]: Malfunction history.
- Result that matters:
- Whether 81-00 remains continuously active or intermittently clears and returns.
- If 81-00 stays active continuously and both space heating and domestic hot water remain stopped, that confirms a persistent R2T circuit open/short or unplugged connector.
- If 81-00 clears automatically and reappears when the backup heater or high-temperature domestic hot water cycle starts, that points to thermal drift in R2T or a heat-sensitive connection.
- Evidence to keep:
- A photo of the 81-00 screen and the sequence of entries in [11] Malfunction history.
Perform this check on the external user interface only; never open the indoor unit front panel or switch box.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
Inspect water temperature values in [6.3] Sensors and note that emergency BUH operation is blocked
- Who:
- The homeowner checking system status on the indoor user interface.
- How:
- Open [6.3]: Information > Sensors to view the reported water temperatures and verify that the system has stopped both space heating and domestic hot water production as documented for 81-00.
- Result that matters:
- Because 81-00 stops both the heat pump and the backup heater for space heating and domestic hot water, forcing backup heater emergency mode will not restore heating while 81-00 is active.
- If both heat pump and backup heater remain stopped while 81-00 is displayed, that confirms the controller's documented protective shutdown for an R2T abnormality.
- If the outdoor temperature is near freezing and the house is losing heat during a prolonged 81-00 shutdown, that indicates the need for urgent installer attendance while leaving main power ON so freeze protection circulation pumps remain powered.
- Evidence to keep:
- A photo of the sensor readings in [6.3] Sensors and the current indoor and outdoor temperatures.
After commissioning, do not turn OFF the power supply; automatic freeze-protection functions require electrical power.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
Retrieve the installer contact from [6.2] Dealer information for an R2T sensor inspection
- Who:
- The homeowner preparing to call the service technician.
- How:
- Open [6.2]: Information > Dealer information on the user interface to get the installer's phone number and write down the exact indoor and outdoor unit model names.
- Result that matters:
- All model references and error history details are ready so the technician can bring a replacement R2T thermistor.
- If you provide code 81-00 and the indoor model code up front, that Confirms the technician can bring the exact R2T backup-heater outlet thermistor for your EPVX/EPSK unit.
- If 81-00 appeared immediately after hydronic servicing or air purging around the backup heater, that suggests the R2T plug or sensor clip may have been disturbed during maintenance.
- Evidence to keep:
- Written notes of the indoor unit model name, serial number, and any recent maintenance work.
Do not attempt to reach the backup heater or thermistor R2T inside the indoor unit yourself.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
Still not solved
If the error persists, stop here. See what the technician must do and show you.
Where this code applies
A code is meaningful only inside the right product and version context.
Primary scope
- System
- Heat pumps
- Brand
- Daikin
- Product type
- Air-to-water heat pump
Known code variants
- Altherma 4 H F 81-00
- code erreur Daikin Altherma 81-00
- codice 81-00 pompa di calore Daikin
- código 81-00 bomba de calor Daikin
- Daikin 81-00
- Daikin Altherma error 81-00
- Daikin Altherma Fehler 81-00
- Daikin heat pump code 81-00
- Daikin Wärmepumpe Fehlercode 81-00
- défaut 81-00 pompe à chaleur Daikin
- error Daikin Altherma 81-00
- errore Daikin Altherma 81-00
What it means
In the Daikin Altherma 4 H F installer reference guide (4PEN773391-1C), code 81-00 is assigned to Exit water temperature thermistor after BUH abnormality when the exit water temperature thermistor downstream of the backup heater is malfunctioning. In the indoor unit piping diagram, thermistor R2T measures Backup heater Water OUT temperature. Unlike return-water sensor faults that allow continued operation, 81-00 stops both the heat pump and the backup heater for space heating and domestic hot water, with automatic reset once the signal returns to normal. The code alone does not prove whether the R2T probe, its internal harness, or the hydro PCB input failed.
Warnings and stop conditions
- Highsource verified
Do not open the indoor unit or switch box: Daikin requires disconnecting all power supplies for more than 10 minutes and measuring less than 50 V DC before touching internal electrical components near the backup heater and PCB.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
- Highsource verified
Never jumper, bypass, or remove thermistor R2T to force the backup heater or heat pump to run; Daikin mandates operating the unit with all thermistors and safety devices connected to prevent overheating.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
Symptoms and causes
Probable causes · in order
- Open circuit, short circuit, or resistance drift in thermistor R2T after the backup heaterCommon
Thermistor R2T, located on the water outlet downstream of the backup heater vessel, has failed electrically or drifted out of range so the controller can no longer verify safe leaving water temperature after the heater.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
- Loose connector, heat-aged wire insulation, or oxidation on the R2T thermistor harnessCommon
Because R2T sits immediately downstream of the backup heater where water temperatures are highest, thermal cycling or vibration can loosen its plug on the indoor PCB or degrade the lead.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
- Poor thermal seating of the R2T thermistor on the backup heater outlet pipePossible
If the R2T retaining clip or pocket loosens after service work on the backup heater or air purge valve, the thermistor reading diverges from actual outlet water temperature.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
- Indoor PCB sensing channel fault on the R2T thermistor inputLess common
If thermistor R2T measures the correct resistance across temperatures and its wiring harness has clean continuity to the board, the analog input stage on the indoor PCB can be defective.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
Virtual technician
Does 81-00 still appear after these checks?
Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.
Sources and technical references
- 1
Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
Daikin Europe N.V. · 2026 · official_doc
Was this entry useful?