U2-44

Daikin Altherma U2-44 supply error: undervoltage in operation

Verified with sources1 sourceReviewed Oct 19, 2026
Technician coming? See the 2 steps they must show you
Air-to-water heat pump outdoor unit next to a house
Mueller felixCC BY-SA 4.0Image source

Risk level

High

Professional inspection is recommended.

Urgency

High

Quick answer

Daikin Altherma 4 H F displays U2-44 when it detects an undervoltage during operation under the supply voltage error group, stopping the heat pump until a manual reset. Check menu [11] Malfunctioning to note when the drop occurred and have an electrician measure supply voltage under load.

Safety first

Stop and check this first

  • Never open the outdoor or indoor switch box yourself: always disconnect the power supply for more than 10 minutes and confirm capacitor voltage is less than 50 V DC before touching electrical parts, and keep unit panels closed so the R290 leak sensor remains effective.
  • Never extend the power supply cable using wire splices or share the heat pump circuit with other appliances, and do not reset U2-44 repeatedly without resolving the cause of the undervoltage.

Safe checks you can perform

  • Read the U2-44 screen in menu [11] Malfunctioning and review [11] Malfunction history
  • Check whether other high-load appliances or shared circuits ran when U2-44 occurred
  • Inspect the visible power supply cable run and verify emergency heating settings in [5.23]

Leave these tasks to a qualified professional

  • Do not attempt this professional task: Measure supply voltage at the outdoor terminals under both standby and full compressor load
  • Do not attempt this professional task: Diagnose the outdoor main PCB A1P voltage sensing circuit per the service manual before manual reset

What a technician must be able to justify

Technician visit

These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.

These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.

  1. Measure supply voltage at the outdoor terminals under both standby and full compressor load

    What they doA qualified electrician or Daikin technician must verify that the circuit is dedicated with no wire-extended cables, isolate the mains for more than 10 minutes until capacitor voltage measures below 50 V DC to inspect and tighten switch box terminals, and then measure live AC voltage at the outdoor unit during compressor ramp-up.

    They must show youThe multimeter voltage reading at the outdoor switch box terminals at rest and during compressor operation compared with the 220-240 V or 380-415 V rating on the identification label..

    In writingBoth the no-load and full-load AC voltage readings, the calculated voltage drop across the feeder, and confirmation that all switch box terminals are tight and free of heat damage..

  2. Diagnose the outdoor main PCB A1P voltage sensing circuit per the service manual before manual reset

    What they doIf the measured AC voltage at the outdoor unit terminals stays within the nameplate range under full load, the Daikin certified technician must follow the model service manual procedure for U2-44 to test the outdoor PCB A1P voltage detection and DC bus circuit before performing a manual reset.

    They must show youThe simultaneously measured terminal AC voltage and the PCB diagnostic reading from the service manual procedure, followed by stable load operation after manual reset..

    In writingThe terminal voltage under load, the service manual test values for PCB A1P, any replaced part numbers, and confirmation that U2-44 did not recur during test heating..

Before accepting a part or repair

Nothing has been shown yet. Do not accept a part swap based on the code alone.

Follow these steps

Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.

  1. Read the U2-44 screen in menu [11] Malfunctioning and review [11] Malfunction history

    No special tools

    Who:
    You or an advanced end user at the indoor MMI interface.
    How:
    Open [11] Malfunctioning, tap the U2-44 message to read the on-screen help text, and with advanced end user permission check [11] Malfunction history for the timestamps of every U2-44 event.
    Result that matters:
    Whether U2-44 occurred once during a known utility dip or repeats whenever the heat pump ramps up for space heating or hot water.
    If U2-44 logged only once during a neighborhood brownout or storm, that points to an external grid voltage sag rather than a fault inside the heat pump.
    If U2-44 returns repeatedly during high-demand heating cycles, that indicates excessive voltage drop under load in the supply wiring, switch box, or outdoor inverter board.
    Evidence to keep:
    Photos of the [11] Malfunctioning help screen and the dated entries in [11] Malfunction history.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C

  2. Check whether other high-load appliances or shared circuits ran when U2-44 occurred

    No special tools

    Who:
    You, reviewing the household distribution panel labels and recent appliance usage without opening any electrical panel.
    How:
    Verify on the breaker directory that the heat pump has its own dedicated circuit and note whether EV chargers, ovens, or electric heaters were running when U2-44 stopped the unit, leaving all heat pump breakers ON.
    Result that matters:
    Whether the heat pump circuit is dedicated and whether heavy building loads coincided with the U2-44 timestamp.
    If the heat pump shares a feeder or trips U2-44 whenever another large domestic appliance runs, that confirms a supply capacity or shared-circuit voltage drop issue.
    If the heat pump sits on a dedicated circuit and no other heavy building loads were active, that rules out domestic branch sharing and focuses the check on feeder resistance, switch box terminals, or PCB A1P.
    Evidence to keep:
    A photo of the breaker board schedule and a note of any high-draw appliances active at the U2-44 timestamp.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C

  3. Inspect the visible power supply cable run and verify emergency heating settings in [5.23]

    No special tools

    Who:
    You, inspecting the exterior cable path from outside and checking the indoor MMI menu.
    How:
    Look along the visible outdoor supply cable for junction boxes or wire extensions, then check [5.23] Settings > Emergency selection on the indoor controller to see whether backup heating is set to cover the stoppage.
    Result that matters:
    Whether the visible supply cable is continuous without wire extensions and how emergency backup heating is configured.
    If the supply cable has been extended with wire splices or shows heat discoloration at an external box, that points to a prohibited cable extension or high-resistance joint causing voltage drop.
    If the external cable run is intact and continuous, that isolates the technician inspection to measured under-load voltage at the outdoor switch box and outdoor PCB A1P.
    Evidence to keep:
    Photos of the outdoor cable entry and a note of the active [5.23] Emergency selection setting.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C

Still not solved

If the error persists, stop here. See what the technician must do and show you.

Where this code applies

A code is meaningful only inside the right product and version context.

Primary scope

System
Heat pumps
Brand
Daikin
Product type
Air-to-water heat pump

Known code variants

  • Altherma 4 H F U2-44
  • code erreur Daikin Altherma U2-44
  • codice U2-44 pompa di calore Daikin
  • código U2-44 bomba de calor Daikin
  • Daikin Altherma error U2-44
  • Daikin Altherma Fehler U2-44
  • Daikin heat pump code U2-44
  • Daikin U2-44
  • Daikin Wärmepumpe Fehlercode U2-44
  • défaut U2-44 pompe à chaleur Daikin
  • error Daikin Altherma U2-44
  • errore Daikin Altherma U2-44

What it means

According to the Daikin Altherma 4 H F installer reference guide, error code U2-44 is classified as a Supply voltage error triggered by Undervoltage during operation, stopping the heat pump until a manual reset. Whereas standby voltage checks only verify no-load mains presence, U2-44 flags that the supply or inverter bus sagged below the minimum operating threshold while the compressor and fans were drawing power. Because an undervoltage under load can stem from a utility brownout, an undersized or wire-extended supply cable, a shared circuit with another appliance, a loose switch box terminal, or an outdoor PCB sensing fault, the code alone never proves the board is defective.

Warnings and stop conditions

  • Highsource verified

    Never open the outdoor or indoor switch box yourself: always disconnect the power supply for more than 10 minutes and confirm capacitor voltage is less than 50 V DC before touching electrical parts, and keep unit panels closed so the R290 leak sensor remains effective.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C

  • Mediumsource verified

    Never extend the power supply cable using wire splices or share the heat pump circuit with other appliances, and do not reset U2-44 repeatedly without resolving the cause of the undervoltage.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C

Symptoms and causes

Probable causes · in order

  • Feeder voltage drop from an extended cable or shared power circuitCommon

    Excessive voltage drop along the supply feeder during high compressor load, caused by an undersized cable, an unauthorized wire-spliced cable extension, or another appliance sharing the same power circuit.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C

  • Utility mains brownout or supply sag during heat pump operationCommon

    A utility grid brownout or temporary supply voltage sag below the identification label rating (220-240 V on 1N~ units or 380-415 V on 3N~ units) while the heat pump was operating.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C

  • High-resistance or loose terminal connection in the switch boxPossible

    A loose terminal screw, oxidized contact, or damaged conductor in the outdoor or indoor switch box introduced series resistance that pulled voltage down when current rose.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C

  • Outdoor main PCB A1P voltage sensing or pre-charge circuit faultLess common

    A fault in the voltage sensing circuit or pre-charge stage on the outdoor main printed circuit board A1P caused the controller to register an undervoltage during operation despite stable mains input.

    Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C

Virtual technician

Does U2-44 still appear after these checks?

Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.