- Heat pumps
- Air-to-water heat pump
UJ20
Daikin Altherma UJ-20: outdoor active filter operation warning

Risk level
Medium
Proceed carefully and stop if the check is unclear.
Urgency
High
Quick answer
Daikin Altherma UJ-20 means the outdoor unit logged an active filter (AF) operation warning while continuing to run and resetting automatically. Record the event count in menu [11] Malfunctioning, check whether other high-draw appliances share the supply, and call a technician if UJ-20 recurs.
Safety first
Stop and check this first
- Never open the outdoor unit switch box or inspect the active filter circuit yourself. Turn off all power supplies, wait more than 10 minutes, and ensure a qualified technician verifies less than 50 V DC before touching any internal electrical parts.
- Do not switch off the outdoor unit circuit breaker to clear UJ-20 while the heat pump is running normally; UJ-20 resets automatically, and cutting mains power disables automatic freeze protection.
Safe checks you can perform
- Check menu [11] Malfunctioning and the malfunction history for UJ-20, UJ-14 or UJ-26
- Confirm in menu [6.3] Sensors that space heating and hot water delivery are unaffected
- Note any heavy electrical equipment or inverters operating on the same property supply
Leave these tasks to a qualified professional
- Do not attempt this professional task: Measure AC supply voltage stability and harmonic quality at the outdoor unit feed
- Do not attempt this professional task: Isolate power for over 10 minutes (<50 V DC) and inspect the active filter wiring and PCB
What a technician must be able to justify
Technician visit
These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.
These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.
Measure AC supply voltage stability and harmonic quality at the outdoor unit feed
What they doA qualified technician or electrician must measure incoming AC voltage under idle and full-load compressor operation at the outdoor unit supply and check for voltage sags or waveform distortion that stress the active filter.
They must show youThe voltage readings at the outdoor supply under compressor load and any logged supply voltage anomalies.
In writingMeasured idle and full-load AC supply voltage (V AC), terminal tightness verification, and assessment of external supply disturbances.
Isolate power for over 10 minutes (<50 V DC) and inspect the active filter wiring and PCB
What they doAfter turning off all power supplies, waiting more than 10 minutes, and measuring less than 50 V DC across the high-voltage capacitors, the technician must inspect the outdoor switch box for thermal discolouration, loose active filter harnesses or capacitor wear, checking whether UJ-14 or UJ-26 are also present.
They must show youThe sub-50 V DC multimeter reading after 10 minutes and the visual condition of the active filter section inside the outdoor switch box.
In writingResidual DC voltage reading (<50 V DC), condition of active filter connectors and components, and test run verification that UJ-20, UJ-14 and UJ-26 remain clear.
Before accepting a part or repair
Nothing has been shown yet. Do not accept a part swap based on the code alone.
Follow these steps
Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.
Check menu [11] Malfunctioning and the malfunction history for UJ-20, UJ-14 or UJ-26
- Who:
- You, reading the indoor user interface menus.
- How:
- Open [11] Malfunctioning to read the long description, and switch user permission to advanced end user to inspect the malfunction history log.
- Result that matters:
- How many times UJ-20 has occurred and whether companion active filter codes UJ-14 (AF communication error) or UJ-26 (AF caution) are also recorded.
- If UJ-20 appeared once and cleared automatically with no UJ-14 or UJ-26 entries, that points to a brief external power quality event.
- If UJ-20 logs repeatedly or appears alongside UJ-14 or supply voltage codes (U2-02, U2-07), that indicates an ongoing supply quality or internal active filter issue.
- Evidence to keep:
- Take a photo of the [11] Malfunctioning description and the complete malfunction history list.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
Confirm in menu [6.3] Sensors that space heating and hot water delivery are unaffected
- Who:
- You, checking the indoor controller sensor display.
- How:
- Open [6.3] Sensors on the user interface to view current leaving water, room and domestic hot water temperatures.
- Result that matters:
- Normal temperature delivery, since chapter 14.4.4 specifies that the unit continues operation during UJ-20.
- If leaving water and tank temperatures match normal targets, that confirms the heat pump is running normally while logging an automatic-reset warning.
- If heating performance is degraded or the unit stops, that points to a separate stopping fault code in the history log that must be addressed first.
- Evidence to keep:
- Note the [6.3] temperature values and the time of observation.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
Note any heavy electrical equipment or inverters operating on the same property supply
- Who:
- You, observing household equipment operation without touching any electrical panels or enclosures.
- How:
- Check whether solar PV inverters, battery storage systems, EV chargers, welders or backup generators were active at the timestamps logged for UJ-20.
- Result that matters:
- Whether UJ-20 correlates with high-draw or inverter-driven equipment on the same mains supply.
- If UJ-20 only logs when a large charger, solar inverter or generator switches on, that suggests external mains waveform distortion triggering the AF warning.
- If UJ-20 occurs at quiet hours with no other equipment running, that rules out domestic interference and points to the outdoor active filter hardware.
- Evidence to keep:
- Keep a written list of the active appliances and timestamps to share with your technician.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
Still not solved
If the error persists, stop here. See what the technician must do and show you.
Where this code applies
A code is meaningful only inside the right product and version context.
Primary scope
- System
- Heat pumps
- Brand
- Daikin
- Product type
- Air-to-water heat pump
Known code variants
- Altherma 4 H F UJ-20
- code erreur Daikin Altherma UJ-20
- codice UJ-20 pompa di calore Daikin
- código UJ-20 bomba de calor Daikin
- Daikin Altherma error UJ-20
- Daikin Altherma Fehler UJ-20
- Daikin heat pump code UJ-20
- Daikin UJ-20
- Daikin Wärmepumpe Fehlercode UJ-20
- défaut UJ-20 pompe à chaleur Daikin
- error Daikin Altherma UJ-20
- errore Daikin Altherma UJ-20
What it means
In chapter 14.4.4 of the Daikin Altherma 4 H F installer reference guide (4PEN773391-1C), code UJ-20 is titled AF warning and is triggered by an active filter operation warning in the outdoor power stage. Together with UJ-14 (AF communication error when the active filter CPU is not communicating) and UJ-26 (AF caution), UJ-20 lets the unit continue operation and uses an automatic reset. An isolated UJ-20 entry does not prove the active filter module or inverter PCB has failed: transient mains waveform distortion, brief voltage sags under compressor load, or loose power harnessing inside the outdoor electrical box can trigger the warning without a permanent board fault.
Warnings and stop conditions
- Highsource verified
Never open the outdoor unit switch box or inspect the active filter circuit yourself. Turn off all power supplies, wait more than 10 minutes, and ensure a qualified technician verifies less than 50 V DC before touching any internal electrical parts.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
- Lowsource verified
Do not switch off the outdoor unit circuit breaker to clear UJ-20 while the heat pump is running normally; UJ-20 resets automatically, and cutting mains power disables automatic freeze protection.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C · Daikin Altherma 4 H F+W+ECH2O operation manual 4PEN773378-1C
Symptoms and causes
Probable causes · in order
- Transient mains voltage distortion or harmonic noise on the power supplyCommon
Voltage dips, switching transients, or harmonic interference on the incoming AC supply force the outdoor active filter (AF) circuit toward its compensation limit, raising an operation warning.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
- High current demand during steep outdoor compressor modulationPossible
Rapid inverter load steps during peak heating or domestic hot water recovery place heavy current stress on the active filter stage.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
- Loose power or signal harness connected to the active filter sectionPossible
Contact resistance or vibration on the internal wiring between the outdoor control section and the active filter stage (related to UJ-14 AF communication error) causes intermittent AF warnings.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
- Degrading capacitor or power component in the active filter moduleLess common
Aging filtering capacitors or switching devices in the outdoor active filter assembly trigger repeated UJ-20 warnings and UJ-26 cautions even when mains power quality is clean.
Evidence: Daikin Altherma 4 H F installer reference guide — 4PEN773391-1C
Virtual technician
Does UJ20 still appear after these checks?
Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.