P8

Mitsubishi Electric P8 on an air conditioner: pipe temperature out of range

Verified with sources1 sourceReviewed Oct 3, 2026
Technician coming? See the 2 steps they must show you
Wall-mounted split air conditioner indoor unit
Dinkun ChenCC BY-SA 4.0Image source

Risk level

High

Professional inspection is recommended.

Urgency

Medium

Quick answer

On Mr. Slim PKA wall units, P8 means the indoor pipe temperature does not reach the expected range in cooling or heating. If the unit was just installed, call the installer; otherwise call a technician. Do not touch the valves or refrigerant.

Safety first

Stop and check this first

  • Mitsubishi Electric requires all supply circuits to be disconnected before reaching the terminals. If refrigerant leaks, ventilate the room: in contact with a flame it releases toxic gases. Board, wiring and refrigerant circuit are technician work.
  • Mitsubishi states this unit uses R410A only. Do not accept a top-up with another gas or without a leak search.

Safe checks you can perform

  • Mode and timing of the code
  • Recent installation or relocation
  • Comparing pipe and room temperature

Leave these tasks to a qualified professional

  • Do not attempt this professional task: Check stop valves and sensor before adding refrigerant
  • Do not attempt this professional task: Leak search and certified recharge

What a technician must be able to justify

Technician visit

These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.

These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.

  1. Check stop valves and sensor before adding refrigerant

    What they doThe technician confirms the stop valves are fully open and the pipe sensor is firmly held before touching the charge.

    They must show youthe pipe and room temperature readings.

    In writingthe state of the valves and the sensor.

  2. Leak search and certified recharge

    What they doIf refrigerant shortage is suspected, the technician finds and repairs the leak and charges only R410A under an F-gas certificate.

    They must show youwhere the leak was.

    In writingamount charged, refrigerant type and certificate number.

Before accepting a part or repair

Nothing has been shown yet. Do not accept a part swap based on the code alone.

Follow these steps

Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.

  1. Mode and timing of the code

    No special tools

    Who:
    you.
    How:
    note whether P8 appears in cooling or heating and how long the unit had been running.
    Result that matters:
    Mitsubishi needs at least 9 minutes in cooling and 27 in heating to detect it, and never flags it in drying mode.
    If it appears in drying mode:
    it is not P8 according to the maker; recheck the code you read.
    If it appears after a while in cooling or heating:
    it fits P8 detection; continue with the checks.
    Evidence to keep:
    a note with mode, start time and time of the code.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

  2. Recent installation or relocation

    No special tools

    Who:
    you.
    How:
    check whether the unit was installed, moved or had refrigerant work shortly before P8 appeared.
    Result that matters:
    whether the fault started right after an intervention.
    If it matches a recent installation:
    call the installer; a stop valve not fully opened is a cause Mitsubishi lists.
    If the unit had run well for a long time:
    the valve is less likely and refrigerant shortage or the sensor gain weight.
    Evidence to keep:
    the installation invoice or job sheet with its date.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

  3. Comparing pipe and room temperature

    Tools required

    Who:
    an F-gas certified air conditioning technician.
    How:
    compares pipe temperature with room temperature using the remote in service mode, switch SW2 on the outdoor board or the PAC-SK52ST tool.
    Result that matters:
    whether the pipe cools or warms as it should with the compressor running.
    If the pipe barely changes:
    it points to a closed valve, refrigerant shortage or the circuit; continue with a leak check.
    If the pipe changes but the reading does not:
    it points to the sensor or its holder.
    Evidence to keep:
    a job sheet with the readings and the method used.

    Requires access to the outdoor board and, for any refrigerant work, an F-gas certificate: technician only.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

Still not solved

If the error persists, stop here. See what the technician must do and show you.

Where this code applies

A code is meaningful only inside the right product and version context.

Primary scope

System
HVAC
Brand
Mitsubishi Electric
Product type
Air conditioner

Known code variants

  • Mitsubishi P8
  • Mr. Slim P8
  • PKA P8

What it means

Mitsubishi Electric defines P8 as a pipe temperature error. In cooling it is detected when the pipe is not in range 3 minutes after the compressor starts and stays out for 6 more minutes (at least 9 minutes in all); in heating, when it is not in range within 20 minutes. It is not detected in drying mode or during defrost. It can come from a loose pipe sensor, refrigerant shortage, a stop valve not fully opened or a refrigerant circuit fault: the code does not say which.

Warnings and stop conditions

  • Highsource verified

    Mitsubishi Electric requires all supply circuits to be disconnected before reaching the terminals. If refrigerant leaks, ventilate the room: in contact with a flame it releases toxic gases. Board, wiring and refrigerant circuit are technician work.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

  • Mediumsource verified

    Mitsubishi states this unit uses R410A only. Do not accept a top-up with another gas or without a leak search.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

Symptoms and causes

Probable causes · in order

  • Stop valve not fully openedPossible

    Typical after a recent installation or relocation: the unit never reaches the expected pipe temperature from its first use.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

  • Refrigerant shortage or circuit faultPossible

    Mitsubishi lists refrigerant shortage and refrigerant circuit defects; only an F-gas certified technician can confirm it and recharge.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

  • Loose pipe sensor or small temperature differencePossible

    If the pipe thermistor holder has come off, or the room is already close to the pipe temperature, the reading does not change enough even with a sound circuit.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

  • Crossed pipes on multi-unit installationsPossible

    Mitsubishi cites reversed extension pipe connection when several units are connected; it only applies to those installations.

    Evidence: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7

Virtual technician

Does P8 still appear after these checks?

Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.

Sources and technical references

Sources: Mitsubishi Electric split-system heat pump service manual OCH639, indoor units PKA-A24KA7, PKA-A30KA7, PKA-A36KA7reviewed 2026-10-03 · verified

Was this entry useful?