3501

SMA inverter event 3501

Verified with sources1 sourceReviewed Aug 23, 2026
Technician coming? See what they must show you
Wall-mounted solar photovoltaic inverter
AsurnipalCC BY-SA 4.0Image source

Risk level

Critical

Stop using the equipment and contact a professional.

Urgency

Immediate

Quick answer

SMA defines event 3501 as: DC-installation insulation resistance is or was too low, often from damaged insulation or a faulty PV connector and sometimes correlated with rain or dew. The useful next discriminator is the affected string, weather correlation and insulation trend. Preserve the event before any reset.

Safety first

What to do now

  • Preserve the exact event context

    Save event 3501, timestamp, inverter model/serial, firmware, red-LED state, affected phase/string, power and weather before clearing anything.

  • Collect one safe discriminator

    Leave feed-in stopped. Record the named string and whether the event follows rain, dew, wind or a recent roof/cable intervention; do not touch DC connectors. Record the affected string, weather correlation and insulation trend; do not change multiple parameters or circuits at once.

  • Respect the electrical stop point

    A cleared event is not proof that insulation is safe. Recurrence, especially with weather, requires per-string measurements before reconnection.

What you must never do

  • Do not attempt this professional task: Measured handoff for SMA 3501

What a technician must be able to justify

A technician is coming

These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.

These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.

  1. Measured handoff for SMA 3501

    What they doUnder the same weather conditions, isolate and measure each indicated string’s insulation resistance and voltages to PE, then inspect connectors, cable runs and modules before reconnecting.

Before accepting a part or repair

Nothing has been shown yet. Do not accept a part swap based on the code alone.

Where this code applies

A code is meaningful only inside the right product and version context.

Primary scope

System
Solar and energy
Brand
SMA
Product type
Solar inverter

Known code variants

  • événement SMA 3501
  • evento SMA 3501
  • inversor SMA 3501
  • inverter SMA 3501
  • onduleur SMA 3501
  • SMA Ereignis 3501
  • SMA event 3501
  • SMA inverter 3501
  • SMA Wechselrichter 3501
  • Sunny Tripower X 3501

What it means

Official meaning: DC-installation insulation resistance is or was too low, often from damaged insulation or a faulty PV connector and sometimes correlated with rain or dew. Decision boundary: capture the affected string, weather correlation and insulation trend. Under the same weather conditions, isolate and measure each indicated string’s insulation resistance and voltages to PE, then inspect connectors, cable runs and modules before reconnecting.

Warnings and stop conditions

  • Criticalsource verified

    PV strings retain hazardous DC voltage in daylight even when the inverter is off. Do not unplug, test or handle strings or connectors.

    Evidence: SMA Sunny Tripower X event messages