CAN Fail

Solis CAN Fail on hybrid inverter: battery CAN link lost

Verified with sources2 sourcesReviewed Oct 18, 2026
Technician coming? See the 2 steps they must show you
Wall-mounted solar photovoltaic inverter
AsurnipalCC BY-SA 4.0Image source

Risk level

Medium

Proceed carefully and stop if the check is unclear.

Urgency

Medium

Quick answer

Solis alarm CAN Fail (also shown as Batt_Comm_FAIL or CAN_Comm_FAIL) means the hybrid inverter cannot communicate over the CAN bus with the battery BMS. Check the battery LEDs and SolisCloud without touching terminals, and call your installer if the alarm persists.

Safety first

Stop and check this first

  • The Solis S6-EH1P manual warns that surfaces can be hot and requires turning off the inverter and waiting 5 minutes before service; disconnecting the battery to measure terminal voltage with a multimeter must only be done by a qualified professional.

Safe checks you can perform

  • Check that the red LED on the battery is not shining or flashing
  • Check BMS Voltage and Battery Voltage in SolisCloud
  • Read the RJ45 cable label and restart after a 5-minute wait

Leave these tasks to a qualified professional

  • Do not attempt this professional task: CAN communication cable replacement or pinout correction
  • Do not attempt this professional task: Physical battery output voltage measurement and model setting check

What a technician must be able to justify

Technician visit

These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.

These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.

  1. CAN communication cable replacement or pinout correction

    What they doThe installer verifies that the cable is plugged into the CAN port on both the battery and the Solis inverter and, on Pylontech US2000C, US3000C or US5000 batteries, replaces it with the updated WIOSCAN30RJ1 cable or alters the pinout to match Solis's diagram.

    They must show youthe cable connected to the CAN ports on both units, the cable part number or pinout, and active BMS data on screen.

    In writingthe RJ45 cable version fitted (such as WIOSCAN30RJ1) and the ports verified on battery and inverter.

  2. Physical battery output voltage measurement and model setting check

    What they doThe technician disconnects the battery from the inverter, measures the voltage at the battery terminals with a multimeter, compares it with Battery Voltage in SolisCloud, and confirms the battery brand selection in the inverter menu.

    They must show youthe multimeter reading at the battery terminals alongside the SolisCloud BMS Voltage and Battery Voltage readings.

    In writingthe measured terminal voltage, the SolisCloud voltage readings and the selected battery model setting.

Before accepting a part or repair

Nothing has been shown yet. Do not accept a part swap based on the code alone.

Follow these steps

Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.

  1. Check that the red LED on the battery is not shining or flashing

    No special tools

    Who:
    you, looking at the battery front panel from outside without disconnecting any cables.
    How:
    follow the Solis Service Center check and look at the battery status lights to confirm the red LED is neither shining nor flashing and the LEDs are green.
    Result that matters:
    finding out whether the battery is too empty to run its BMS communication.
    If the red LED on the battery is shining or flashing:
    Solis states the battery is too empty to work and needs charging with an external charger by a professional until the LEDs return to green.
    If the battery LEDs are green:
    the battery has charge and the issue lies in the CAN link or settings, so check the voltages in SolisCloud next.
    Evidence to keep:
    a photo of the battery indicator LEDs and the alarm text on the Solis inverter screen.

    Evidence: Pylon US2000C/US3000C/US5000 Battery - Batt_Comm_FAIL - No Battery

  2. Check BMS Voltage and Battery Voltage in SolisCloud

    No special tools

    Who:
    you, using the SolisCloud app or web portal.
    How:
    open SolisCloud, go to the battery monitoring section and select both BMS Voltage and Battery Voltage to see whether the system detects the battery and whether No Battery is also logged.
    Result that matters:
    seeing whether the inverter reads terminal voltage while BMS Voltage is missing due to the CAN failure.
    If BMS Voltage is missing or significantly lower than expected:
    this matches the CAN communication issue described by Solis.
    If both voltages match and the alarm has cleared:
    note the time in case the drop was brief.
    Evidence to keep:
    a SolisCloud screenshot with both BMS Voltage and Battery Voltage plotted.

    Evidence: Pylon US2000C/US3000C/US5000 Battery - Batt_Comm_FAIL - No Battery

  3. Read the RJ45 cable label and restart after a 5-minute wait

    No special tools

    Who:
    you, checking the outer label on the data cable without touching DC power terminals.
    How:
    look for a serial label on the RJ45 cable (WIOSCAN30RJ1 new version vs WIOSCAN35RJ3 old version); if your installer showed you how to power-cycle the inverter, Table 7.1's note says to turn off the inverter and wait 5 minutes before restarting.
    Result that matters:
    ruling out a temporary latch-up and identifying whether an older Pylontech cable is fitted.
    If the cable is marked WIOSCAN35RJ3 or the alarm remains after a 5-minute restart:
    contact your installer or distributor.
    If communication resumes after the 5-minute restart:
    confirm in SolisCloud that BMS telemetry stays stable.
    Evidence to keep:
    a photo of the RJ45 cable label, the Solis inverter serial number and the installation date.

    Evidence: User Manual for S6 Series Hybrid Inverter S6-EH1P(3-8)K-L-PLUS Version 1.3, Release Date: 04,2026 · Pylon US2000C/US3000C/US5000 Battery - Batt_Comm_FAIL - No Battery

Still not solved

If the error persists, stop here. See what the technician must do and show you.

Where this code applies

A code is meaningful only inside the right product and version context.

Primary scope

System
Solar and energy
Brand
Solis (Ginlong)
Product type
Solar inverter

Known code variants

  • Batt_Comm_FAIL Solis
  • CAN_Comm_FAIL Solis
  • fallo comunicación CAN batería Solis S6-EH1P
  • Solis Batt_Comm_FAIL
  • Solis CAN Fail
  • Solis CAN_Comm_FAIL
  • Solis híbrido CAN Fail No Battery
  • Solis hybrid battery CAN communication failure
  • Solis S6-EH1P CAN Fail

What it means

In the Solis S6-EH1P(3-8)K-L-PLUS hybrid inverter user manual (Version 1.3, April 2026, Table 7.1) and the Solis Service Center article on Pylontech US2000C, US3000C and US5000 batteries (updated 2025-03-05), CAN Fail (or 'Batt_Comm_FAIL', previously 'CAN_Comm_FAIL') indicates a communication failure on the Controller Area Network (CAN) bus between the inverter and the battery's Battery Management System (BMS), which can also trigger a follow-up 'No Battery' alarm. Solis links it to a faulty cable, wrong port connection, an incompatible RJ45 cable version, or a powered-off or deeply discharged battery. The code alone never proves the inverter or battery is defective.

Warnings and stop conditions

  • Highsource verified

    The Solis S6-EH1P manual warns that surfaces can be hot and requires turning off the inverter and waiting 5 minutes before service; disconnecting the battery to measure terminal voltage with a multimeter must only be done by a qualified professional.

    Evidence: User Manual for S6 Series Hybrid Inverter S6-EH1P(3-8)K-L-PLUS Version 1.3, Release Date: 04,2026 · Pylon US2000C/US3000C/US5000 Battery - Batt_Comm_FAIL - No Battery

Symptoms and causes

Probable causes · in order

  • Damaged CAN cable or plug inserted into the wrong portCommon

    Table 7.1 of the S6-EH1P manual explains that CAN Fail occurs when the cable is in poor condition or is not plugged into the CAN port on both the battery and the inverter.

    Evidence: User Manual for S6 Series Hybrid Inverter S6-EH1P(3-8)K-L-PLUS Version 1.3, Release Date: 04,2026

  • Outdated or incompatible RJ45 battery communication cableCommon

    Solis notes that some batteries require a special manufacturer cable; on Pylontech US2000C, US3000C and US5000 units, the older WIOSCAN35RJ3 cable must be replaced with the updated WIOSCAN30RJ1 cable or re-pinned.

    Evidence: User Manual for S6 Series Hybrid Inverter S6-EH1P(3-8)K-L-PLUS Version 1.3, Release Date: 04,2026 · Pylon US2000C/US3000C/US5000 Battery - Batt_Comm_FAIL - No Battery

  • Battery powered off, deeply discharged or wrong battery model setPossible

    The Solis Service Center article explains that a powered-off battery, a battery with its red LED shining or flashing because it is too empty, or wrong inverter battery settings will prevent BMS detection.

    Evidence: User Manual for S6 Series Hybrid Inverter S6-EH1P(3-8)K-L-PLUS Version 1.3, Release Date: 04,2026 · Pylon US2000C/US3000C/US5000 Battery - Batt_Comm_FAIL - No Battery

Virtual technician

Does CAN Fail still appear after these checks?

Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.

Sources and technical references