PE Fault
myenergi zappi PE Fault (Fault code 25) on an EV charger: earth connection problem

Risk level
High
Professional inspection is recommended.
Urgency
High
Quick answer
The zappi found a problem with the main earth connection: disconnected or with too high an impedance. Unplug the car and do not charge again until an electrician has checked the earth.
Safety first
Stop and check this first
- Do not charge with PE Fault active: the charger earth protects against shock from the car body and the cable.
- According to myenergi, disabling the PE check by choosing IT Earthing is only valid after a qualified electrician's checks. It is not a user fix.
Safe checks you can perform
- Unplug the car and reset
- Recent electrical work
- Earth continuity and impedance measurement
- zappi earthing setting
Leave these tasks to a qualified professional
- Do not attempt this professional task: Protective conductor continuity
- Do not attempt this professional task: Earth loop impedance and earthing system
- Do not attempt this professional task: RCD trip test on the charger circuit
What a technician must be able to justify
Technician visit
These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.
These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.
Protective conductor continuity
What they doThe electrician measures earth continuity from the consumer unit to the zappi terminals with an installation tester.
They must show youthe continuity reading in ohms against the permitted value.
In writingpoint measured, value obtained and any connection corrected.
Earth loop impedance and earthing system
What they doMeasures earth loop impedance at the charger and identifies whether the supply is TN, TT or IT.
They must show youthe impedance reading and the system identified.
In writingmeasured value against the applicable limit and the conclusion.
RCD trip test on the charger circuit
What they doTests the RCD or RCBO protecting the zappi circuit with an RCD tester.
They must show youthe measured trip time.
In writingdevice type, test current and time against the specification.
Before accepting a part or repair
Nothing has been shown yet. Do not accept a part swap based on the code alone.
Follow these steps
Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.
Unplug the car and reset
- Who:
- you, no tools.
- How:
- unplug the car and press and hold the zappi reset button, as the manual says.
- Result that matters:
- whether PE Fault returns after the reset.
- If it does not return:
- still note it; a repeated earth alert needs inspection.
- If it returns:
- confirms a persistent earth or settings problem; stop charging.
- Evidence to keep:
- photo of the PE Fault screen and the date.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
Recent electrical work
- Who:
- you, no tools.
- How:
- recall any recent changes to the consumer unit, the incoming supply or the charger installation.
- Result that matters:
- whether PE Fault started right after work was done.
- If it matches recent work:
- points to a disturbed earth connection; tell the electrician.
- If nothing changed:
- the origin may be the supply or the zappi setting.
- Evidence to keep:
- dates of work and who did it.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
Earth continuity and impedance measurement
- Who:
- qualified electrician.
- How:
- measure protective conductor continuity to the zappi and earth loop impedance with an installation tester.
- Result that matters:
- measured values against your wiring rules and the earthing system type.
- If continuity fails:
- confirms a disconnected or loose earth.
- If continuity is fine but impedance is high:
- points to the supply characteristics, not the charger.
- Evidence to keep:
- report with readings and the earthing system identified.
Measuring earth and opening the charger or consumer unit is electrician work. You do not touch cables or terminals.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
zappi earthing setting
- Who:
- electrician or installer, never the user.
- How:
- in the installer settings, confirm Supply Grid / Earthing matches the real supply earthing system.
- Result that matters:
- the setting matches the measured installation.
- If the supply is IT and the setting does not reflect it:
- explains the alert with no physical fault.
- If the setting is correct:
- moves the focus back to the physical earth.
- Evidence to keep:
- photo of the setting before and after, with the reason.
myenergi only considers disabling the PE check (IT Earthing option) after a qualified electrician has completed all standard checks. Do not change it yourself.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
Still not solved
If the error persists, stop here. See what the technician must do and show you.
Where this code applies
A code is meaningful only inside the right product and version context.
Primary scope
- System
- EV charging
- Brand
- myenergi
- Product type
- EV charger
Known code variants
- zappi earth fault
- zappi error 25 tierra
- zappi fallo de tierra
- zappi fault code 25
- zappi PE Fault
- zappi PE not connected
What it means
myenergi defines Fault code 25 as a problem with the zappi main earth connection: the earth is disconnected or its impedance is too high. The PE check measures the impedance of the supply back to the transformer. It can trip on a loose earth conductor, on a high impedance earthing system or on a wrong earthing setting. The code does not say which.
Warnings and stop conditions
- Higheditorial warning
Do not charge with PE Fault active: the charger earth protects against shock from the car body and the cable.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
- Mediumsource verified
According to myenergi, disabling the PE check by choosing IT Earthing is only valid after a qualified electrician's checks. It is not a user fix.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
Symptoms and causes
Probable causes · in order
- Earth conductor disconnected or loosePossible
This is the first cause myenergi gives: earth does not reach the zappi. Only an electrician can confirm it with a continuity measurement.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
- Earth impedance too high in the installationPossible
The earth exists but its impedance exceeds what the PE check accepts. myenergi says this is rare and depends on the supply characteristics.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
- Earthing system set wrongly on the zappiPossible
If the supply is IT earthed, myenergi says to check the Supply Grid / Earthing setting. If the setting does not match the real installation, the alert can appear with no physical fault.
Evidence: zappi eco-smart EV charge point User Manual Rev 2.2 July 2023 · PE Fault
Virtual technician
Does PE Fault still appear after these checks?
Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.