- EV charging
- EV charger
0x2000
ABB Terra AC 0x2000 on an EV charger: one or more phases missing

Risk level
Medium
Proceed carefully and stop if the check is unclear.
Urgency
Medium
Quick answer
The Terra AC detects that one or more phases are missing from its supply (Missing phase). Check whether a protective device for the charger is off and contact an electrician, as ABB says.
Safety first
Stop and check this first
- If a charger protective device tripped by itself, do not reset it repeatedly. ABB refers this code to a qualified electrical contractor.
Safe checks you can perform
- Charger protective device status
- Other three-phase equipment
- Phase measurement at the charger input
Leave these tasks to a qualified professional
- Do not attempt this professional task: Per-phase voltage at origin and charger
- Do not attempt this professional task: Connections, protection and insulation
What a technician must be able to justify
Technician visit
These are the steps they must carry out and show you. Tick them as they work: if steps are skipped, do not accept a part swap.
These are not instructions for opening or handling the equipment yourself. They are the checks that should support a technical conclusion.
Per-phase voltage at origin and charger
What they doThe electrician measures each phase to neutral at the main consumer unit and at the Terra AC input.
They must show youreadings for each phase at both points.
In writingmissing phase, where it is lost and the correction made.
Connections, protection and insulation
What they doWith the circuit isolated, checks connection tightness and circuit protection, and measures insulation resistance.
They must show youthe connection or device corrected and the insulation reading.
In writingitems checked and values against wiring rules.
Before accepting a part or repair
Nothing has been shown yet. Do not accept a part swap based on the code alone.
Follow these steps
Note: Follow the documented order. An error code identifies the affected system, but it does not prove by itself which part has failed.
Charger protective device status
- Who:
- you, looking at the consumer unit only.
- How:
- check whether any device on the Terra AC circuit is off.
- Result that matters:
- all devices are on.
- If one is off:
- note it and tell the electrician before resetting it if it tripped by itself.
- If all are on:
- the phase is missing in the connections or the supply.
- Evidence to keep:
- photo of the consumer unit.
Evidence: User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
Other three-phase equipment
- Who:
- you, no tools.
- How:
- if you have other three-phase equipment, see whether it works normally.
- Result that matters:
- whether only the charger is affected.
- If it also fails:
- points to the supply; tell the network operator and the electrician.
- If it works:
- points to the charger circuit.
- Evidence to keep:
- note of which equipment fails.
Evidence: User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
Phase measurement at the charger input
- Who:
- qualified electrician.
- How:
- measure each phase voltage at the consumer unit and at the Terra AC input.
- Result that matters:
- which phase is missing and where it is lost.
- If it is already missing at the main consumer unit:
- confirms a supply problem.
- If it is only missing at the charger:
- confirms a circuit connection or device.
- Evidence to keep:
- report with readings per phase.
Measuring phases is mains voltage work. Electrician only.
Evidence: User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
Still not solved
If the error persists, stop here. See what the technician must do and show you.
Where this code applies
A code is meaningful only inside the right product and version context.
Primary scope
- System
- EV charging
- Brand
- ABB
- Product type
- EV charger
Known code variants
- ABB Terra AC 0x2000
- ABB Terra AC Missing phase
- Terra AC error 0x2000
- Terra AC error 0x2000 falta de fase
What it means
In the Terra AC user manual (revision 004), 0x2000 is Missing phase: one or more phases are missing. It affects models supplied with more than one phase. The phase can be missing because of a tripped device, a loose connection or a supply problem. The code does not say which, nor which phase is missing. The code table depends on the manual edition: the 2020 Spanish installation manual assigns different meanings to some hexadecimal codes. Always compare with the manual for your unit.
Warnings and stop conditions
- Mediumeditorial warning
If a charger protective device tripped by itself, do not reset it repeatedly. ABB refers this code to a qualified electrical contractor.
Evidence: User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
Symptoms and causes
Probable causes · in order
- One phase device trippedPossible
If a device on the charger circuit is off at the consumer unit, it explains the missing phase.
Evidence: User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
- Loose connection in the circuitPossible
If devices are on and the phase does not reach the charger, it points to a circuit connection. The electrician measures it.
Evidence: User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
- Phase missing on the supplyPossible
If other three-phase equipment in the home also fails, the phase is already missing at the service head.
Evidence: User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
Virtual technician
Does 0x2000 still appear after these checks?
Answer a few questions to narrow down the likely cause and the safest next action. Guidance only - it never replaces a professional.
Sources and technical references
- 1
User manual Terra AC (BCM.V3Y00.0-EN, revision 004)
ABB E-mobility · 2023 · manual